Wire Gauge Chart Master Guide: AWG to mm² Conversion & Ampacity Tables (2025)
Expert Insight: “In my 20 years of inspecting electrical systems—from industrial plants in North Carolina to high-rise apartments in Ho Chi Minh City—the number one cause of electrical fires isn’t faulty devices; it’s undersized wiring. This guide isn’t just a chart; it’s your safety manual.”
– Lead Engineer, KTH Electric Co., Ltd.

Mục lục
ToggleThe Critical Importance of Correct Wire Sizing
Imagine this scenario: You’ve just installed a powerful new tankless water heater or a high-end car audio system. You flip the switch, everything works for ten minutes, and then—darkness. Or worse, the smell of burning insulation fills the air. This is the reality of ignoring the Wire Gauge Chart.
In the world of electrical engineering, wire gauge is not merely a suggestion; it is a dictate of physics. Whether you are a DIY enthusiast looking up 12 volt wire size chart by distance or a professional calculating the 100 amp service entrance wire size, understanding the relationship between the diameter of a conductor and its current-carrying capacity (Ampacity) is non-negotiable.
Safety Risks of Undersized Conductors
When current flows through a wire, it encounters resistance. This resistance generates heat. A wire that is too thin (undersized) for the load acts less like a conductor and more like a heating element in a toaster. If the heat exceeds the temperature rating of the insulation (typically 60°C, 75°C, or 90°C), the insulation melts, leading to short circuits, arc faults, and catastrophic fires. The National Electrical Code (NEC) exists primarily to prevent this specific failure mode.
Efficiency Losses and Voltage Drop
Safety is paramount, but efficiency is the silent killer of performance. You might have safe wiring that doesn’t catch fire, but if it’s slightly undersized for the distance, you suffer from Voltage Drop.
- In homes: Your lights dim when the AC kicks on.
- In tools: Your saw runs slower and burns out its motor prematurely.
- In audio: Your expensive speakers sound muddy because the amplifier is starving for power.
Choosing the correct gauge ensures that the energy you pay for actually reaches the device, rather than being wasted as heat in the walls.
Overview of AWG (American) vs. IEC (Metric) Standards
For our global readers, and specifically those navigating between equipment standards in Vietnam (Metric) and the US (Imperial), confusion is common.
AWG (American Wire Gauge):
Used primarily in North America. The key rule to remember is the inverse relationship: The higher the number, the thinner the wire. (e.g., 18 AWG is thinner than 10 AWG).
IEC 60228 (Metric):
Used in Vietnam and Europe. This is straightforward; wire is measured by its Cross-Sectional Area in square millimeters ($mm^2$). The bigger the number, the thicker the wire.
Below, we bridge these two worlds with precise conversion data.
The Ultimate Wire Gauge Charts (Reference Data)
As an engineer, I know you often just need the numbers. Below are the three most critical charts for any electrical work. Bookmark this section for your field reference.
Chart 1: Standard American Wire Gauge (AWG) Dimensions
This chart defines the physical properties of the wire. Note how the resistance drops drastically as the wire gets thicker (lower gauge number).
| AWG Size | Diameter (mm) | Diameter (inches) | Area (mm²) | Resistance (mΩ/m) | Max Freq (Skin Depth) |
|---|---|---|---|---|---|
| 0000 (4/0) | 11.68 | 0.4600 | 107.0 | 0.1608 | 125 Hz |
| 000 (3/0) | 10.40 | 0.4096 | 85.0 | 0.2028 | 160 Hz |
| 00 (2/0) | 9.266 | 0.3648 | 67.4 | 0.2557 | 200 Hz |
| 0 (1/0) | 8.252 | 0.3249 | 53.5 | 0.3224 | 250 Hz |
| 2 | 6.544 | 0.2576 | 33.6 | 0.5127 | 410 Hz |
| 4 | 5.189 | 0.2043 | 21.2 | 0.8152 | 650 Hz |
| 6 | 4.115 | 0.1620 | 13.3 | 1.296 | 1.1 kHz |
| 8 | 3.264 | 0.1285 | 8.37 | 2.061 | 1.7 kHz |
| 10 | 2.588 | 0.1019 | 5.26 | 3.277 | 2.7 kHz |
| 12 | 2.053 | 0.0808 | 3.31 | 5.211 | 4.4 kHz |
| 14 | 1.628 | 0.0641 | 2.08 | 8.286 | 6.9 kHz |
| 16 | 1.291 | 0.0508 | 1.31 | 13.17 | 11 kHz |
| 18 | 1.024 | 0.0403 | 0.823 | 20.95 | 17 kHz |
| 20 | 0.812 | 0.0320 | 0.518 | 33.31 | 27 kHz |
| 22 | 0.644 | 0.0253 | 0.326 | 52.96 | 42 kHz |
| 24 | 0.511 | 0.0201 | 0.205 | 84.22 | 67 kHz |
Chart 2: AWG to mm² Conversion Table (Vietnam Standard Focus)
In Vietnam, if you ask for “14 gauge wire” at a local hardware store, you might get a blank stare. You need to ask for “2.5 mm²”. However, they are not exactly identical. This chart shows the nearest metric equivalent commonly used in trade.
| AWG Size | Exact Area (mm²) | Nearest Metric Standard (mm²) | Common Application (Vietnam/IEC) |
|---|---|---|---|
| 18 AWG | 0.82 | 0.75 or 1.0 | Lamp cords, low power lighting control. |
| 16 AWG | 1.31 | 1.5 | Lighting circuits, switch legs. |
| 14 AWG | 2.08 | 2.5 | Standard wall outlets (Ổ cắm), general power. |
| 12 AWG | 3.31 | 4.0 | Air conditioners (AC), Water heaters, Kitchen outlets. |
| 10 AWG | 5.26 | 6.0 | Large AC units, Electric stoves, Sub-panels. |
| 8 AWG | 8.37 | 10.0 | Service entrance, Shower heaters (Direct). |
| 6 AWG | 13.30 | 16.0 | Main distribution boards, Industrial motors. |
| 4 AWG | 21.15 | 25.0 | Main grounding, Heavy industrial feeds. |
| 2 AWG | 33.62 | 35.0 | Battery banks, Large inverter connections. |
| 1/0 AWG | 53.49 | 50.0 | Service mains for large villas/buildings. |
Engineer’s Note: Never “round down” when converting. If the calculation calls for 10 AWG (5.26 mm²), do not use 4.0 mm² wire just because it is close. You must move up to 6.0 mm² to ensure safety.
Chart 3: Ampacity Ratings (Current Carrying Capacity)
This is the “Holy Grail” for electricians—derived from NEC Table 310.16. It answers the question: “How many amps can this wire handle?”
Note: These values assume Copper conductors, not more than 3 current-carrying conductors in a raceway, based on 30°C ambient temperature.
| AWG Size | Copper (60°C / TW, UF) | Copper (75°C / THW, THWN) | Copper (90°C / THHN, XHHW-2) | Circuit Breaker Size (Typical) |
|---|---|---|---|---|
| 14 | 15 A | 20 A† | 25 A† | 15 Amps |
| 12 | 20 A | 25 A† | 30 A† | 20 Amps |
| 10 | 30 A | 35 A† | 40 A† | 30 Amps |
| 8 | 40 A | 50 A | 55 A | 40-50 Amps |
| 6 | 55 A | 65 A | 75 A | 60 Amps |
| 4 | 70 A | 85 A | 95 A | 80-90 Amps |
| 3 | 85 A | 100 A | 115 A | 100 Amps |
| 2 | 95 A | 115 A | 130 A | 110-125 Amps |
| 1 | 110 A | 130 A | 145 A | 125-150 Amps |
Engineering Deep Dive: How to Interpret the Data
Key Concept
The AWG system is logarithmic: every 3-step decrease in gauge doubles the cross-sectional area and halves the resistance, drastically improving efficiency.
Charts are useful, but understanding the physics empowers you to troubleshoot unique situations. Here is what we look at behind the scenes at KTH Electric.
The Inverse Relationship Rule
The American Wire Gauge system is logarithmic. For every 3 steps you go down in gauge (e.g., from 14 to 11), the cross-sectional area doubles, and the resistance is cut in half. Conversely, for every 3 steps up (thinner wire), resistance doubles.
Key takeaway: A 10 gauge wire has roughly half the resistance of a 13 gauge wire (or effectively 1/1.6 of a 12 gauge). This is why jumping just one size makes a massive difference in voltage drop performance.
Solid vs. Stranded Wire Diameter Variances
You will often see two diameters listed for the same gauge.
- Solid Wire: A single piece of copper. The diameter is exactly as the chart says.
- Stranded Wire: Multiple small strands twisted together. Because there are air gaps between the strands, the overall outer diameter is slightly larger than a solid wire of the same gauge, even though the amount of copper (cross-sectional area) is effectively the same.
Application Tip: When pulling wire through conduit (pipe), stranded wire is flexible and easier to pull around corners, but solid wire is easier to terminate on standard wall outlets and switches.
Skin Effect in High-Frequency Applications
If you look at Chart 1, you see a column for “Max Frequency”. In standard 50Hz/60Hz home wiring, the current uses the entire cross-section of the wire. However, as frequency increases (like in audio signals or high-speed data), electricity tends to travel only on the outer surface (“skin”) of the conductor.
Relevance: This is why thick, solid cables are great for power but arguably overkill or inefficient for high-frequency data unless specifically designed (like coaxial cable). For standard house wiring, Skin Effect is negligible.
Advanced Sizing Factors (Beyond the Basic Chart)
Critical Calculation
Never rely solely on ampacity charts for long runs; calculate voltage drop (< 3% for electronics) and derate capacity for hot environments or bundled conduits.
Simply picking a wire based on the ampacity chart above is only Step 1. If you stop there, you risk failure in long-distance runs or hot environments.
Calculating Voltage Drop for Long Distance Runs
All wire has resistance. Over a long distance, that resistance eats up voltage.
- The 3% Rule: For sensitive electronics (computers, modern washing machines with erratic boards), the voltage drop should not exceed 3%.
- The 5% Rule: For general loads (lights, heaters) and the total drop from the service entrance to the final outlet, do not exceed 5%.
Formula: V_drop = (2 × L × R × I) / 1000
(Where L is length in feet, R is resistance from Chart 1, and I is current in Amps).
Example: You are running a 20A circuit to a shed 100 feet away using 12 AWG wire (1.6 Ω/1000ft).
$V_{drop} = \frac{2 \times 100 \times 1.6 \times 20}{1000} = 6.4 \text{ Volts}$.
On a 120V circuit, that is a 5.3% drop. This is marginal. If you upgrade to 10 AWG (1.0 Ω/1000ft), the drop becomes only 4 Volts (3.3%), which is much safer and more efficient.
Ambient Temperature Correction
The charts above assume an ambient temperature of 30°C (86°F).
Practical Applications & Selection Guide
Field Guide
Match the wire to the voltage context: 220V systems allow for thinner wires than 12V DC systems for the same power load due to lower current draw.
Theory is essential, but application is where the rubber meets the road. Depending on whether you are wiring a villa in Ho Chi Minh City (220V) or a workshop in North Carolina (120V/240V), the amperage load for the same appliance will differ, influencing your wire gauge choice.
Residential Wiring (220V AC Context)
In Vietnam and most of Europe/Asia, the standard voltage is 220V. This is an advantage over the US 120V system because doubling the voltage halves the current for the same wattage. This allows for slightly smaller conductors for equivalent power loads, but safety standards remain strict.
- Lighting Circuits (1.5 mm² / 16 AWG): For standard LED lighting or ceiling fans, the load is typically low. A 1.5 mm² wire is the industry standard here. It is easy to manipulate into switch boxes and capable of handling up to 10-13 Amps safely, which is more than enough for modern lighting zones.
- General Wall Outlets (2.5 mm² / 14 AWG): Never use less than 2.5 mm² (approx. 14-13 AWG) for wall sockets. You never know what a user will plug in—a vacuum cleaner, an iron, or a space heater. This wire size is rated for roughly 16-20 Amps, providing a necessary safety buffer for high-draw appliances.
- Air Conditioners & Water Heaters (4.0 mm² / 12-10 AWG): For a 1.5 HP or 2.0 HP air conditioner, or a storage water heater, 4.0 mm² wire is the professional choice. These devices have high “in-rush” currents when the compressor or heating element kicks on. Using thinner wire here is the leading cause of melted terminal blocks and fire hazards.
Automotive and Low Voltage (12V/24V DC)
This is where many DIYers fail. In a 12V DC system (cars, boats, solar batteries), voltage drop is your worst enemy. A 2-volt drop in a 220V house system is negligible (0.9%). A 2-volt drop in a 12V car system is a 16% loss, causing lights to dim and pumps to fail.
- Battery Cables & Starters: These require massive cables, typically 4 AWG, 2 AWG, or 1/0 AWG. The starter motor draws hundreds of amps for a few seconds; thin wire will simply act as a fuse and melt.
- LED Light Bars & Audio: Never rely on the factory harness if you are extending the distance. For a 20A light bar run of 15 feet, you should use at least 12 AWG to maintain brightness, whereas in a house, 12 AWG would carry that same current for 50+ feet.
Extension Cords and Portable Power
We have all seen it: a cheap, orange extension cord getting warm when running a power saw. That heat is wasted energy and a melting hazard.
- Light Duty (Lamps): 18 AWG or 16 AWG (up to 25ft).
- Medium Duty (Drills, Saws): 14 AWG (up to 50ft).
- Heavy Duty (Compressors, Table Saws): 12 AWG or 10 AWG.
Common Mistakes in Wire Selection
Critical Error: Do not confuse linear diameter with cross-sectional area, ensure insulation matches the environment (THHN vs UF), and never mix copper with aluminum without rated bi-metal connectors.
Even experienced apprentices make these errors. Avoiding them separates the professionals from the risky amateurs.
1. Confusing Diameter with Cross-Sectional Area
This is classic confusion between linear width and square area. Doubling the diameter of a wire actually quadruples its area (and thus its current capacity).
Example: A 2mm diameter wire is not “twice as good” as a 1mm diameter wire; it is roughly four times better in terms of conductivity. Always calculate based on area ($mm^2$) or strict AWG charts, not by “eyeballing” the thickness.
2. Ignoring Insulation Types (THHN vs. UF vs. PVC)
The copper carries the current, but the insulation determines the environment.
- THHN/THWN: Standard for running inside conduit (pipes). The nylon coating makes it slick and easy to pull, and it has a high heat rating ($90^\circ$C).
- UF-B (Underground Feeder): Designed for direct burial in the dirt. You cannot use standard indoor wire underground; moisture will eventually penetrate the insulation and cause a ground fault.
- Standard PVC (Vietnam): Often rated for $70^\circ$C. Be careful not to apply NEC $90^\circ$C ampacity tables to standard PVC wire, or you will overheat the insulation.
3. Mixing Copper and Aluminum without Approved Connectors
Aluminum wire is cheaper and lighter, making it popular for main service entries. However, Copper and Aluminum react chemically when they touch (Galvanic Corrosion). This corrosion creates resistance, then heat, then fire.
The Fix: If you must connect them, use special bi-metal connectors (rated “AL/CU”) and apply an anti-oxidant paste (like Noalox). Never twist them together directly with a standard wire nut.
FAQ: Frequently Asked Questions about Wire Gauges
FAQ Summary
Quick clarifications: 12 AWG is thicker than 14 AWG, 10 AWG is limited to 30A breakers, and welding cable is generally not code-compliant for house wiring.
Q: Is 12 AWG bigger than 14 AWG?
A: Yes. In the American Wire Gauge system, the smaller the number, the thicker the wire. 12 AWG is approximately 60% thicker (in area) than 14 AWG and can handle 20 Amps compared to 14 AWG’s 15 Amps.
Q: How many amps can a 10 gauge wire handle?
A: According to NEC standards, 10 AWG copper wire is rated for 30 Amps for general circuit use. While the physics of the wire might allow slightly more in free air, breakers for 10 AWG wire must be sized at 30A to ensure safety.
Q: What is the metric equivalent of 12 gauge wire?
A: 12 AWG is 3.31 mm². In metric markets (like Vietnam), you won’t find 3.31 mm². The closest standard size is 4.0 mm², which is slightly larger and safer. In some commercial applications, 2.5 mm² is sometimes pushed to replace 12 AWG, but this is a downgrade in capacity.
Q: Can I use welding cable for house wiring?
A: generally, No. While welding cable is incredibly flexible and has high ampacity, its insulation is usually not rated for the same fire resistance, smoke generation, or physical damage protection required by building codes for permanent in-wall installation.
📥 Don’t Rely on Memory in the Field
Job sites, basements, and industrial plants often have poor signal. Don’t risk guessing wire sizes when safety is on the line. We have compiled the complete AWG to mm² Conversion Table and NEC Ampacity Limits into a single, high-resolution Engineering Pocket Guide.
*Optimized for mobile viewing & high-quality printing • 1.2 MB
Conclusion: Ensuring Electrical Integrity and Safety
Final Thought
Safety is non-negotiable; always verify calculations against standard charts and consult professionals for complex installations.
The Wire Gauge Chart is more than just a list of numbers; it is the foundation of electrical safety. Whether you are calculating the voltage drop for a solar array or simply replacing a socket in your bedroom, respecting the limits of your conductors is the only way to ensure your system runs cool, efficient, and fire-free for decades.
At KTH Electric, we don’t guess. We calculate. If you are planning a complex electrical installation—whether it’s a new factory setup in Vietnam or a residential upgrade in the US—don’t risk using the wrong chart.
Need professional advice? Contact our engineering team today:
Company: KTH Electric Co., Ltd.
🇻🇳 Vietnam Head Office:
251 Pham Van Chieu, An Hoi Tay Ward, Ho Chi Minh City
Hotline: 0968.27.11.99
Email: kthelectric.com@gmail.com

REVIEWED BY:
DR. KHUONG NGUYEN-VINH
✓ Verified Expert
Dr. Khuong Nguyen-Vinh is a Lecturer in Electronic & Computer Systems Engineering at RMIT University Vietnam, dedicated to bridging the gap between advanced theory and practical energy solutions.
With a Ph.D. in Electrical Power Engineering from VSB – Technical University of Ostrava, his research focuses on intelligent control systems for renewable energy, including AI-driven fault detection for solar panels and optimized MPPT algorithms.
💡
Expert Commitment:
“A committed educator, Dr. Khuong mentors the next generation of engineers in power electronics, embedded systems, and sustainable technology integration for Industry 4.0.”
Related
Discover more from KTH Electric Co., Ltd.
Subscribe to get the latest posts sent to your email.